Reliable Single Interlock Preaction System Manual de servicio Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 64
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
Page 17
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
February, 2010
PREACTION SPRINKLER
SYSTEM
With the Model G-2000, G-3000, or G-4000 Valve: When the detector operates, the solenoid valve
opens (Figure 10d). Prime water is drained from the prime chamber, causing the G series valve to
open, filling the sprinkler piping with water. Water from the intermediate chamber of the G series valve
pressurizes the sensing end of the PORV, causing the PORV to open, which continually vents
prime water pressure (Figure 10d).
Figure 10d: Single Interlock System with Electric Release System using a Model G Series Valve
Vista de pagina 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 63 64

Comentarios a estos manuales

Sin comentarios